About this product
True RMS measurements and optimized ergonomics make the 324 Plus Clamp Meter an ideal troubleshooting tool for commercial and residential electricians. The 324 Plus is built to verify the presence of load current, AC voltage and continuity of circuits, switches, fuses and contacts.
This small and rugged clamp meter is ideally suited for current measurements up to 400 A in tight cable compartments. The Fluke 324 plus model also includes temperature and capacitance measurement capabilities.
Specifications
- AC Current
- Range: 600.0 A
- Resolution: 0.1 A
- Accuracy: 2 % ± 5 digits (48 – 62 Hz)
- Crest Factor: (50/60 Hz) 2.5 @ 600 A
- AC Voltage
- Range: 600.0 V
- Resolution: 0.1 V
- Accuracy: 1.0 % ± 5 digits (48 – 62 Hz)
- DC Voltage
- Range: 600.0 V
- Resolution: 0.1 V
- Accuracy: 1 % ± 5 digits
- Resistance
- Range: 600.0 Ω/6000 Ω
- Resolution: 0.1 Ω/1 Ω
- Accuracy: 1 % ± 5 digits
- Continuity Beeper: 30 Ω
- Capacitance
- Range: 10.0 – 100.0 μF / 1000 μF
- Resolution: 0.1 μF/1 μF
- Accuracy: 1.9 % ± 2 digits
- Environmental Specifications
- Operating Temperature: -10 °C to +50 °C
- Storage Temp: -40 °C to +60 °C
- Operating Humidity: Non condensing (< 10 °C) ≤ 90 % RH (at 10 °C to 30 °C) ≤ 75 % RH (at 30 °C to 40 °C) ≤ 45 % RH (at 40 °C to 50 °C) (Without Condensation)
- Operating Altitude: 3000 meters
- Storage Altitude: 12,000 meters
- EMI, EMC: Meets all applicable requirements in EN61326-1:2006
- Temperature Coefficients: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
- Safety Compliance: ANSI/ISA S82.02.01:2004 CAN/CSA-C22.2 No. 61010-1-04 IEC/EN 61010-1:2001, 600V CAT III, 300V CAT IV Pollution Degree 2 EN/IEC 61010-2-32:2002 EN/IEC 61010-031:2002/A1:2008
- Batteries: 2 AA, NEDA 15A, IEC LR6