About this product
The FC Wireless Industrial System displays the readings wirelessly on the 3000 FC Wireless Digital Multimeter. De-energize the cabinet, connect the remote modules, close the cabinet and reenergize.
Connect the three FC Wireless iFlex AC Current Module to your test points, and view the results from all three phases in less time and cost of current test methods or connect the FC Wireless AC Voltage Module and view both voltage and current measurements simultaneously. Get answers, faster, and spend less time in full PPE.
From short distances, you can even view readings from modules through closed electrical panels. The Fluke Connect remote modules captures up to 65,000 sets of time stamped min/max/avg readings, using the optional PC adapter. Fluke Connect wireless test tools offer increased safety by letting you view readings in a separate location.
Specifications
- AC Voltage
- Range / Resolution: 600.0 mV / 0.1 mV, 6.000 V / 0.001 V, 60.00 V / 0.01 V, 600.0 V / 0.1 V, 1000 V / 1 V
- Accuracy: 45 Hz to 500 Hz 1.0% + 3, 500 Hz to 1 kHz 2.0% + 3
- mV
- Range / Resolution: 600.0 mV / 0.1 mV
- Accuracy: 0.09% + 2
- V
- Range / Resolution: 6.000 V / 0.001 V, 60.00 V / 0.01 V, 600.0 V / 0.1 V, 1000 V / 1 V
- Accuracy: 0.09% + 2, 0.15% + 2
- )))
- Range / Resolution: 600 Ω / 1 Ω
- Accuracy: Meter beeps at < 25 Ω, beeper detects opens or shorts of 250 μs or longer.
- Ω
- Range / Resolution: 600.0 Ω / 0.1 Ω, 6.000 kΩ / 0.001 kΩ, 60.00 kΩ / 0.01 kΩ, 60.00 kΩ / 0.1 kΩ, 600.0 kΩ / 0.001 MΩ, 50.00 MΩ / 0.01 MΩ
- Accuracy: 0.5% + 2, 0.5% + 1, 1.5% + 3
- Diode Test
- Range / Resolution: 2.000 V / 0.001 V
- Accuracy: 1% + 2
- µF
- Range / Resolution: 1000 nF / 1 nF, 10.00 μF / 0.01 μF, 100.0 μF / 0.1 μF, 9999 μF1 / 1 μF
- Accuracy: 1.2% + 2, 10% typical
- AC and DC Current
- mA AC (45 Hz to 1 kHz)
- Range1 / Resolution: 60.00 mA / 0.01 mA, 400.0 mA3 / 0.1 mA
- Accuracy: 1.5% + 3
- mA DC2
- Range1 / Resolution: 60.00 mA / 0.01 mA, 400.0 mA3 / 0.1 mA
- Accuracy: 0.5% + 3
- Frequency
- Range / Resolution: 99.99 Hz / 0.01 Hz, 999.9 Hz / 0.1 Hz, 9.999 kHz / 0.001 kHz, 99.99 kHz / 0.01 kHz
- Accuracy: 0.1% + 1
- mA Function
- Overload Protection: Fused, 44/100 A, 1000 V FAST Fuse
- Overload: 600 mA overload for 2 minutes maximum, 10 minutes rest minimum
- MIN/MAX Recording Accuracy
- DC Functions: ± 12 counts for changes > 350 mS in duration.
- AC Functions: ± 40 counts for changes > 900 mS in duration.
- Maximum Voltage Between any Terminal and Earth Ground: 1000 V DC or AC RMS
- Ω Fuse Protection From A Inputs: 0.44 A (44/100 A, 440 mA), 1000 V FAST Fuse, Fluke specified part only
- Display (LCD)
- Update Rate: 4/sec
- Volts, Amps, Ohms: 6000 counts
- Frequency: 10,000 counts
- Capacitance: 1,000 counts
- Battery Type: Three AA Alkaline batteries, NEDA 15A IEC LR6
- Battery Life: 250 hours minimum
- RF Communications: 2.4 GHZ ISM Band
- RF communication Range
- Open Air, Unobstructed: Up to 20m
- Obstructed, Sheetrock Wall: Up to 6.5m
- Obstructed, Concrete Wall, or Steel Electrical Enclosure: Up to 3.5m
- Temperature
- Operating: -10°C to 50°C
- Storage: -40°C to 60°C
- Temperature Coefficient: 0.1 X (specified accuracy) / °C (< 18°C or > 28°C)
- Relative Humidity: 0% to 90% (0°C to 35°C), 0% to 75% (35°C to 40°C), 0% to 45% (40°C to 50°C)
- Altitude
- Operating: 2,000 m
- Storage: 12,000 m
- Electromagnetic Compatibility
- EMI, RFI, EMC, RF: EN 61326–1:2006, EN 61326–2–2:2006, ETSI EN 300 328 V1.7.1:2006, ETSI EN 300 489 V1.8.1:2008, FCC Part 15 Subpart C Sections 15.207, 15.209, 15.249
- FCCID : FCC: T68–FDMMBLE IC: 6627A–FDMMBLE
- Safety Compliance: ANSI / ISA 61010–1 / (82.02.01): 3rd edition
- CAN / CSA-C22.2 No 61010-1-12: 3rd edition
- UL 61010–1: 3rd edition
- IEC / EN 61010–1:2010
- Certifications: CSA, FCC, CE
- Ingress Protection (IP) Rating: IP54
- Pollution Degree: 2