Description
The Fluke i800 AC Current Clamp is made for use with multimeters, recorders, safety testers, etc., for accurate non-intrusive AC current measurement. Extend the current measuring capability of a digital multimeter to 800 A AC.
Compatible with digital mulitmeters that accepts shrouded 4 mm (0.16) banana plugs that have an AC milliamp range.
Continuous Current Range: 100 mA to 800 A rms
Maximum Non-Destructive Current: 1500 A rms (50/60 Hz)
Lowest Measurable Current: 100 mA
Basic Accuracy: 1% of reading
Usable Frequency: 30 Hz - 10 kHz (-3dB)
Output Level(s): 1 mA / A
Safety: CAT III 600 V
Maximum Voltage: 600 V AC rms or DC
Maximum Conductor Diameter: 54 mm (2.13 in)
Output cable length: 1.6 m (63 in)
Lead connector: Shrouded banana plugs
Compatible with digital mulitmeters that accepts shrouded 4 mm (0.16) banana plugs that have an AC milliamp range.
Specifications
Nominal Current Range: 800 A rmsContinuous Current Range: 100 mA to 800 A rms
Maximum Non-Destructive Current: 1500 A rms (50/60 Hz)
Lowest Measurable Current: 100 mA
Basic Accuracy: 1% of reading
Usable Frequency: 30 Hz - 10 kHz (-3dB)
Output Level(s): 1 mA / A
Safety: CAT III 600 V
Maximum Voltage: 600 V AC rms or DC
Maximum Conductor Diameter: 54 mm (2.13 in)
Output cable length: 1.6 m (63 in)
Lead connector: Shrouded banana plugs